Diesel Generator Sets
C9 Generator Set
-
Maximum Rating300 ekW
-
Minimum Rating180 ekW
-
EmissionsEU Stage IIIA, Low Fuel
-
Voltage220 to 480 Volts
Generator Set Specifications
- Maximum Rating
- 300 ekW
- Minimum Rating
- 180 ekW
- Emissions
- EU Stage IIIA, Low Fuel
- Voltage
- 220 to 480 Volts
- Frequency
- 60 Hz
- Speed
- 1800 rpm
- Duty Cycle
- Standby, Prime
Engine Specifications
- Engine Model
- C9 ATAAC, I-6, 4-Stroke Water-Cooled Diesel
- Bore
- 4.41 in
- Stroke
- 5.87 in
- Displacement
- 537.01 in³
- Compression Ratio
- 16.1:1
- Aspiration
- Air to Air Aftercooled
- Fuel System
- Hydraulic electronic unit injection
- Governor Type
- Adem™A4
Generator Set Dimensions
- Length
- 157 in
- Width
- 47.5 in
- Height
- 73.5 in
-
Air Inlet System
- Air cleaner, light duty with disposable paper filter
- Turbocharger
- Air cleaner, light duty with disposable paper filter
-
Control Panels
- GCCP 1.3
- EMCP4.4 control panel
-
Cooling System
- Radiator and cooling fan with guard
- Fan drive, battery charging alternator drive
- Coolant drain line with valve
- Caterpillar extended life coolant
- Radiator and cooling fan with guard
-
Exhaust System
- Stainless steel exhaust flex, gaskets, rain cap & SAE exhaust flange for customer use - shipped loose
- Flange for customer; shipped loose
- Stainless steel exhaust flex, gaskets, rain cap and SAE exhaust
-
Fuel System
- Standard open set fuel tank/base supplied
- Base, formed steel with single wall integral 8-hour fuel tank
- Standard open set fuel tank/base supplied
- Base, formed steel with single wall integral 8-hour fuel tank
-
Generators and Generator Attachments
- Mandatory option circuit breaker, IEC, 3 pole mounted in power centre
- Power centre, IP22
- Voltage regulator (single phase sensing)
- 12 Leads
- IP23 Protection
- Segregated low voltage (AC/DC) wiring panel
- IP23 Protection
- 12 Leads
-
Governing System
- Cat electronic governor (ADEM A4)
- Cat electronic governor (ADEM A4)
-
Lube System
- Oil cooler
- Lubricating oil
- Oil drain valves
-
Mounting System
- Captive linear vibration isolators between base and engine-generator
- Includes lifting provisions and termination points for coolant and lube oil drain lines
-
Starting / Charging System
- 24V battery with rack and cables
-
General
- Engine and alternator re-paint, Caterpillar yellow
- Engine and alternator re-paint, Caterpillar yellow
-
Certifications
- European Certificate for Conformance
- Global Certification for CIS
-
Air inlet system
- Single element air cleaner
-
Circuit breakers
- 4 Pole (IEC-100% rated) Circuit breaker upgrades: 400, 630, 800 and 100 amps
-
Control Panels
- Oil temperature displays
- Control panel protective devices: Earth fault relay ; Earth leakage ground fault ; overload shutdown via breaker ; Low fuel level shutdown ; Low fuel level alarm ; Fuel level sensor
-
Cooling System
- Radiator duct flange
- Low coolant temperature alarm
-
Enclosures
- Sound attenuated enclosure
- High ambient sound attenuated enclosure
-
Exhaust System
- Mufflers - End in/end out; 10 dBA or 25 dBA attenuation
- 5 and 6 inch elbow kits
- 6 inch flange
- 5 - 6 inch flange adaptor
-
Fuel System
- Integral dual wall fuel tank base
-
Generators and Attachments
- Permanent magnet excitation (PMG) generator
- Oversize, AREP, CIP generators
-
Mounting System
- Narrow skid base
-
Starting / Charging System
- Battery disconnet switch
- Jacket water heater
- 5 Amp single Battery charger