Diesel Generator Sets
C18 Generator Set
-
Maximum Rating600 ekW
-
Minimum Rating455 ekW
-
EmissionsU.S. EPA Cert., Tier 2
-
Voltage208 to 600 Volts
Generator Set Specifications
- Maximum Rating
- 600 ekW
- Minimum Rating
- 455 ekW
- Emissions
- U.S. EPA Cert., Tier 2
- Voltage
- 208 to 600 Volts
- Frequency
- 60 Hz
- Speed
- 1800 rpm
- Duty Cycle
- Standby, Prime
Engine Specifications
- Engine Model
- C18 ATAAC, I-6, 4-Stroke Water-Cooled Diesel
- Bore
- 5.71 in
- Stroke
- 7.2 in
- Displacement
- 1106.4 l
- Compression Ratio
- 14.5:1
- Aspiration
- Air to Air Aftercooled
- Fuel System
- Electronic unit injection
- Governor Type
- Adem™A4
- Bore
- 145 mm (5.71 in)
- Displacement
- 18.13 L (1106.36 in3)
- Stroke
- 183 mm (7.2 in)
Generator Set Dimensions
- Length
- 5550 in
- Width
- 80.9 in
- Height
- 107.8 in
-
Air Inlet
- Air cleaner
-
Air Inlet System
- Turbocharger
- Light duty air cleaner
- Aftercooler core
-
Cooling
- Caterpillar extended life coolant
- Fan drive, battery charging alternator drive
- Coolant drain line with valve
- Radiator and cooling fan with guard
- Package mounted radiator
-
Exhaust
- Exhaust flange outlet
-
Exhaust System
- Stainless steel exhaust flex gaskets, raincap and SAE exhaust flange for customer use - shipped loose
-
Fuel System
- Standard 8 hour open set fuel tank
-
Fuel
- Secondary fuel filters
- Fuel priming pump
- Primary fuel filter with integral water separator
-
Generator and Attachments
- Matched to the performance and output characteristics of Cat engines
- Segregated low voltage (AC/DC) wiring panel
- Power center, IP22
- A Frame generator - IP21 protection
- Integrated voltage regulator (IVR)
- Mandatory option circuit breaker, IEC, 3 pole, mounted in power centre
- Integrated voltage regulator (IVR)
-
Generator
- IP23 Protection
- Matched to the performance and output characteristics of Cat engines
- Load adjustment module provides engine relief upon load impact and improves load acceptance and recovery time
-
Power Termination
- Busbar
-
Control System
- GCCP 1.2
-
Governing System
- Cat electronic governor (ADEM A4)
-
Control Panel
- EMCP 4 Genset controller
-
Lube System
- Lubricating oil
- Oil drain valves
-
Mounting System
- Captive linear vibration isolators between base and engine-generator. includes lifting provisions and termination points for coolant and lube oil drain lines
-
Mounting
- Rubber vibration isolators
-
Starting/Charging
- 24 Volt battery with rack and cables
- 24 volt starting motor
- Batteries
-
General
- Engine and alternator pre-paint, Caterpillar yellow
- Paint - Caterpillar yellow except rails and radiators gloss black
-
Air Inlet System
- Single element air cleaner
- Dual element air cleaner
-
Exhaust
- Industrial, residential, critical mufflers
-
Generator
- Oversize and premium generators
- Excitation: [ ] Permanent magnet excitation (PMG) Excited (PM) [ ] Internally Excited (IE)
- Anti-condensation heater
-
Power Termination
- Circuit breakers, UL listed
- Circuit breakers, IEC compliant
-
Circuit breakers
- 3 Pole (IEC-100% rated) Circuit breakers - Motorised
- 4 Pole (IEC-100% rated) Circuit breakers - Motorised
- Shunt trip for IEC breaker
- Power terminal strip
- Circuit breaker (IEC) Auxiliary contacts
- 3 Pole (IEC-100% rated) Circuit breakers - Package mounted
- Padlockable circuit breaker device
- 4 Pole (IEC-100% rated) Circuit breakers - Package mounted
-
Control Panels
- Remote monitoring software
- Load share module
- Local & remote annunciator modules
- GCCP 1.2, GCCP 1.5
- Digital I/O module
-
Control System
- Local alarm modules
- Volt free contact
- Local alarm horn
- Remote annunciator module
- Oil temperature displays
- Protective devices: Earth fault relay - earth leageage Ground fault relay - Overload shutdown via breaker - Low fuel level alarm - Low fuel level shutdown - High fuel level alarm - Fuel level sensor
- GCCP 1.5
-
Cooling System
- Low coolant temperature alarm
- Radiator duct flange
-
Enclosures
- Sound attenuated enclosures
-
Starting/Charging
- Jacket water heater
- Battery chargers
- Heavy duty starting system
- Oversize batteries
- Charging alternator
-
Exhaust System
- 8 and 10 inch GP flanges
- 8 and 10 inch elbow kits
- Engine mounted muffler
- 10, 25 and 35 end in / end out mufflers
- Manifold and turbocharger guards
-
Fuel System
- Manual fuel transfer pump
- Fuel transfer system
- Integral - Dual wall fuel tank base
-
General
- Sound attenuated, weather protective or high ambient weather protective enclosure
- Integral & sub-base UL listed dual wall fuel tanks
- CSA Certification
- Automatic transfer switches (ATS)
- The following options are based on regional and product configuration:
- Single or dual wall sub-base fuel tanks
- EU Certificate of Conformance (CE)
- EEC Declaration of Conformity
- UL 2200 package
- Single or dual wall integral fuel tanks
- Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
- Narrow, wide or skid base
- Enclosures: Sound attenuated, weather protective
-
Generator and Attachments
- Space heaters
- A Frame CIP generator
- Permanent magnet excitation (PMG)
- LC frame generator
- A Frame oversize generator
- Ingress protection
- LC frame CIP generator
- LC frame oversize generators
-
Lube System
- Manual sump pump
-
Starting and Charging
- Battery disconnect switch
- Jacket water heaters
- 5 Amp Battery charger