Piscataway Campus
732-885-5555
Bensalem Campus
877-726-7663

Diesel Generator Sets

3412C Generator Set

  • Maximum Rating
    800 ekW
  • Minimum Rating
    635 ekW
  • Emissions
    Low Fuel Consumption
  • Voltage
    220 to 480 Volts
Generator Set Specifications
Maximum Rating
800 ekW
Minimum Rating
635 ekW
Emissions
Low Fuel Consumption
Voltage
220 to 480 Volts
Frequency
60 Hz
Speed
1800 rpm
Duty Cycle
Standby, Prime
Engine Specifications
Engine Model
3412C TA, V-12, 4-Stroke Water-Cooled Diesel
Bore
5.4 in
Stroke
6 in
Displacement
1648.86 in³
Compression Ratio
13:00:01
Aspiration
TA
Fuel System
Pump and Lines
Governor Type
ADEM™ A5
Generator Set Dimensions
Length
162.4 in
Width
78.3 in
Height
75 in
Dry Weight
5761 lb
Dry Weight
13275 lb
  • Air Inlet System
    • Air cleaner, single element canister type
    • Single element canister type
  • Control Panel
    • High coolant temperature
    • Customer data link (Modbus RTU)
    • Low coolant temperature
    • Low coolant level
    • Communications:
    • Run/auto/ stop/control
    • Engine cycle crank
    • Generator temperature monitoring module
    • Power factor (per phase & average)
    • Remote CAN annunciator
    • Serial annunciator module data link
    • DC volts
    • Frequency (Hz)
    • Operating hours.
    • Emergency stop pushbutton
    • Digital I/O module
    • Local annunciator
    • Low oil pressure
    • Oil pressure (psi, kPa or bar)
    • Emergency stop
    • Warning shutdowns:
    • Volts (L-L & L-N)
    • Remote Serial annunciator
    • Speed adjust
    • Amps (per phase & average)
    • Voltage adjust
    • EMCP 4.2B
    • Overspeed
    • coolant temperature
    • Digital Indicator for:
    • RPM
    • Accessory module data link
    • Failure to start (overcrank)
    • Controls:
    • Compatible with the following optional modules:
  • Cooling System
    • Caterpillar extended life coolant
    • Radiator with guard (sized for 50 degrees C)
    • Fan and belt guards
    • Coolant drain line with valve
  • Exhaust System
    • Stainless steel exhaust flex with ANSI style outlet flange
  • Fuel System
    • Primary and Secondary fuel filters
    • Fuel priming pump
    • Water separator
  • Generator and Attachments
    • 3 Phase sensing
    • SR4B self excited
    • Class F temperature rise
    • VR6B voltage regulator
    • Busbar termination
    • 12 Leads
    • Class H insulation
    • 2:1 Volts/Hz
    • Reactive droop
  • Governing System
    • Cat electronic governor
  • Lube System
    • Oil drain line with valve
    • Lubricating oil
    • Oil filter
  • Mounting System
    • Base, formed steel with linear vibration isolators between base and engine-generator
  • Starting / Charging System
    • Battery with rack, cables
    • 45 Amp Charging alternator
    • Fuel shutoff solenoid
    • 24 Volt starting motor
  • General
    • Paint - Caterpillar yellow except rails and radiators gloss black
  • Air Inlet System
    • Air cleaner - Dual element
    • Air cleaner - Heavy element
    • Air cleaner - single element
  • Certificates
    • EU Certification
  • Circuit breakers
    • 4 Pole Circuit breakerswith shunt trip
    • 3 Pole Circuit breakers with shunt trip
    • Power terminal strip
  • Control Panel
    • EMCP 4.3, EMCP 4.4
    • Temperature monitoring package
    • Vandal proof panel door
    • Generator running VFC
    • Earth leakage Ground fault relay
    • Common alarm/shutdown relay
  • Cooling System
    • Jacket water heater
    • Radiator duct flange
    • Radiator removal
  • Exhaust System
    • Muffler 10 dBA attenuation
    • Manifold and turbocharger guards
    • Muffler 35 dBA attenuation
    • Elbow mounting kit
    • Through wall installation kit
  • Fuel System
    • Manual fuel transfer pump
    • Automatic fuel transfer system
  • Generator and Attachments
    • Internal excitation (IE)
    • Anti-condensation heater
    • Permanent magnet excitation (PMG)
    • Oversize and premium generators
  • Governing System
    • Electronic load share
  • Lube System
    • Manual sump pump
  • Mounting System
    • Fuel tank base (1200 Ltr)
  • Special Tests / Reports
    • PGS Test report @ 1.0 power factor
    • PGS Test report @ 0.8 power factor
    • Factory witness test
  • Starting / Charging system
    • Oversize battery set
    • Battery chargers
    • Heavy duty starting system
    • Battery disconnect switch
    • Battery removal
  • Enclosures
    • DC lighting package
    • Weather protective enclosure (WP)
    • Sound attenuated enclosure (SA)