Diesel Generator Sets

3516C Tier 4 Final

  • Standby Rating
    2500/2000 ekW
  • Prime Power Rating
    1825/2250 ekW
  • Emissions
    U.S. EPA Certified
  • Voltage
    480 to 13800 Volts
Generator Set Specifications
Standby Rating
2500/2000 ekW
Prime Power Rating
1825/2250 ekW
Emissions
U.S. EPA Certified
Voltage
480 to 13800 Volts
Frequency
60 Hz
Speed
1800 rpm
Duty Cycle
Standby, Mission Critical, Prime
Maximum Rating
2500 ekW
Minimum Rating
1825 ekW
Engine Specifications
Engine Model
3516C HD, ATAAC, V-16, 4-Stroke Water-Cooled Diesel
Bore
6.69 in
Stroke
8.46 in
Displacement
78 in
Compression Ratio
14.7:1
Aspiration
TA
Fuel System
Electronic unit injection
Governor Type
ADEM™A4
Displacement
4764.73 in³
Stroke
8.46 in
Exhaust Flange Size
203.2 mm (8.0 in)
Aspiration
TA
Fuel System
Electronic unit injection
Bore
6.69 in
Displacement
4764.73 in3
Stroke
8.46 in
Generator Set Dimensions
Length
267.6 in
Length
277 in
Width
93.7 in
Width
101.2 in
Height
116.7 in
Height
118.9 in
Dry Weight
37200 lb
Dry Weight
40280 lb
  • Air Inlet System
    • Air cleaner; single element canister type
  • Cooling
    • Package mounted radiator
  • Exhaust
    • Exhaust flange outlet
  • Control Panels
    • Generator phase sequence
    • 1 Programmable digital outputs
    • KAR / PF modes
    • Low coolant temperature
    • PLC functionality
    • Generator mounted - Rear facing
    • Environmental sealed front face
    • Generator set packages include:
    • Auto/start/stop control
    • Customer data link (Modbus RTU)
    • High coolant temperature
    • Warning/shutdown with common LED indication of shutdowns for:
    • 0 True RMS AC metering, 3-phase, +/-2% accuracy
    • Low coolant level
    • Operating hours
    • kVAr (per phase, average & percent)
    • RFI suppression
    • Emergency stop
    • Digital indication for:
    • Amps (per phase & average)
    • Min / max exciter
    • Number of I/O varies on options selected
    • Load histogram feature
    • Frequency (Hz)
    • Overcurrent (50/51)
    • Oil pressure (psi, kPa or bar)
    • Lamp test
    • Engine cool-down timer
    • Cat connect
    • kW-hr (total) - kVAr-hr (total)
    • Limiter and exciter diode monitor
    • Communications:
    • Over/under frequency (81 o/u)
    • 6 Customer programmable digital inputs
    • Controls:
    • Overspeed
    • IVR includes reactive droop capability
    • Low oil pressure
    • RPM
    • 24 Volt DC operation
    • Volts (L-L & L-N)
    • Text alarm/event descriptions
    • 1 Programmable relay outputs (Form C)
    • Controls: Speed adjust
    • Reverse reactive power (kVAr) (32RV)
    • Power factor (per phase & average)
    • High coolant temperature
    • Accessory module data link
    • Customizable screens
    • 4 programmable relay outputs (Form A)
    • Caterpillar's voltage regulator
    • Programmable protective relaying functions
    • Alarm acknowledge
    • Over/under voltage (27/59)
    • DC volts
    • kVA (per phase, average & percent)
    • Failure to start (overcrank)
    • Engine cycle crank
    • 3 Phase voltage sensing
    • Coolant temperature
    • Serial annunciator module data link
    • Emergency stop pushbutton
    • Reverse power (kW) (32)
    • kW (per phase, average & percent)
    • 3 Analog inputs
  • Fuel
    • Primary fuel filter with integral water separator
  • Generator
    • Matched to the performance and output characteristics of Cat engines
    • IP23 Protection
  • Power Termination
    • Busbar
  • Control Panel
    • Cat ECS Genset controller
  • Cooling System
    • Certified standard PGS provided
  • Exhaust System
    • Flanged faced outlet(s)
    • Dry exhaust manifold
  • Fuel System
    • Fuel cooler; not included with packages without radiator
    • Secondary fuel filters
    • Fuel priming pump
    • Flexible fuel lines - shipped loose
  • General
    • Right hand servicing
    • Caterpillar yellow with high gloss black rails and radiator
    • Paint - Caterpillar yellow except rails and radiators gloss black
    • Flywheel and flywheel housing - SAE No. 00
    • SAE standard rotation
  • Generator and Attachments
    • Form wound
    • High voltage:
    • NEMA standard hole pattern
    • Class H insulation, Class F temperature rise at 40C ambient (105C prime/130C standby)
    • Low voltage: Random wound - Internal excitation (IE) - Winding temperature detectors - NEMA Class H insulation system, Class H temperature rise at 40C ambient (125C prime/150C standby) - Busbar connections, top center mounted, top cable entry - NEMA standard hole pattern
    • Permanent magnet excitation (PMG)
    • Medium voltage:
    • 6 Lead
    • 3 Phase brushless, Salient pole
    • Busbar connections, right side extension box, bottom cable entry
    • NEMA Class H insulation system, Class H temperature rise at 40C ambient (125C prime/150C standby)
    • Permanent magnet excitation (PMG)
    • Anti-condensation space heater
    • Winding temperature detectors
  • Governing System
    • ADEM A3
  • Literature
    • Parts book
  • Lubrication System
    • Integral lube oil cool
    • Oil drain lines and valve
    • Gear type lube oil pump
    • Fumes disposal
    • Lubricating oil
    • Oil filter, filler and dipstick
  • Mounting System
    • Rails - engine/generator/radiator mounting
    • Anti-vibration mounts (shipped loose)
    • Rubber anti-vibration mounts - shipped loose
  • Starting System
    • Battery and battery rack w/cables
    • 45 Amp Charging alternator
    • 24 Volt electric starting motor
    • Battery disconnect switch
  • Control System
    • EMCP 4.4
  • Air Inlet System
    • Single element filter
    • Dual element air cleaner
  • Exhaust
    • Exhaust mufflers
  • Generator
    • Internal excitation (IE)
    • Anti-condensation heater
    • Oversize and premium generators
    • Permanent magnet excitation (PMG)
  • Cooling System
    • Coolant
    • Water level switch gauges
    • Standard ambient radiators
    • Optional installed ATAAC radiators
    • Optional installed radiators
    • Standard ambient ATAAC radiators
  • Power Termination
    • Circuit breakers, UL listed
    • Circuit breakers, IEC compliant
  • Crankcase System
    • No explosion relief valves
    • Explosion relief valves
    • Ventilation system
  • Control Panels
    • Remote monitoring software
    • Digital I/O module
    • Generator temperature monitoring & protection
    • Load share module
  • Exhaust System
    • Tier 4 clean emissions module
    • Flexible fittings
    • Flanges
    • Tier 4 clean emission MOD Kits
    • Mufflers
    • Tier 4 dosing cabinet
    • Flange and exhaust expanders
    • Clean emission parts
    • Exhaust offset
    • Y Adapters
    • Elbows
  • Mounting
    • IBC isolators
  • Starting/Charging
    • Battery chargers
    • Heavy duty starting system
    • Charging alternator
    • Air starting motor with control and silencer
    • Oversize batteries
  • Fuel System
    • Primary fuel filter
    • Fuel priming pumps (Tier 4) - Manual or electric
  • General
    • Automatic transfer switches (ATS)
    • The following options are based on regional and product configuration:
    • EEC Declaration of Conformity
    • Enclosures: Sound attenuated, weather protective
    • UL 2200 package
    • US aid emblem
    • Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
    • EU Certificate of Conformance (CE)
    • Integral & sub-base UL listed dual wall fuel tanks
    • CSA Certification
    • Special paint (Colors other than Caterpillar yellow or high performance paints)
    • Integral & sub-base fuel tanks
  • Generators and Attachments
    • Low / Medium voltage: 380, 416, 440, 480, 600, 2400, 4160 Volts, 3 Phase 1800 RPM, FW, PM, No. of Leads = 6, Pitch = .6667: 1600, 1800 Frame
    • Generator conversion
    • Thermostat for space heater
    • Alternator air cleaner
    • Differential current transformers (DCT) 8.7 kV and 15 kV classes
    • Space heater kit
    • High voltage: 6300, 6600, 6900 volts, 3 phase 1800 rpm, FW, PM, No. of Leads = 6, Pitch = .6667: 2700, 3000 Frame
    • High voltage: 12470, 13200, 13800 volts, 3 phase 1800 rpm,FW, PM, No. of Leads = 6, Pitch = .6667: 2700, 3000 Frame
    • Low / Medium voltage: 380, 440, 480, 600 volts, 3 phase 1800 rpm. RW, IE, No. of Leads = 6, Pitch = .6667: 1600 Frame
  • Instrumentation
    • Pyrometer and thermocouples
  • Lubrication System
    • Lube oil in standard sump
    • Prelube pumps
    • Oil level regulator
  • Mounting System
    • IBC vibration isolators
    • Spring type vibration isolators
    • Puck style low efficiency isolators
  • Power Connections
    • Ground cables between generator and terminal box
    • Right side power connections
    • 2700 Frame, four lead, four terminal
    • Neutral ground connections
    • Center post busbars
    • Rear power connections
    • Left side power connections
    • Low voltage Circuit breakers
  • Special Tests / Reports
    • PGS Test report @ 1.0 power factor
    • IBC Certification
    • Canadian Standards Association certification
    • PGS Test report @ 0.8 power factor
    • Generator set fuel consumption test
    • Generator test report
    • Torsional vibration analysis reports
    • Standard engine test charge
    • OSHPD Certification
    • Fuel consumption test
  • Starting and Charging
    • Jacket water heaters
    • Electric starting motors
    • Air starting motors
    • 10, 20, 35 and 50 Amp Battery chargers
    • Air pressure regulator
    • 24 Volt battery set - Dry
    • Engine barring device
    • Starter cover
  • Extended Service Coverage
    • Platinum, Gold and Silver coverage