Electric Power

Cat XLM Switchgear

  • Configuration
    Traditional customizable PLC based floor standing switchgear capable of controlling and monitoring multiple utilities, generators, and loads
  • Configuration
    Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications
  • Modes of Operation
    Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power
  • Modes of Operation
    Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power
Technical Summary
Configuration
Traditional customizable PLC based floor standing switchgear capable of controlling and monitoring multiple utilities, generators, and loads
Configuration
Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications
Modes of Operation
Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power
Modes of Operation
Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power
Application
LV and MV ( 208V - 38 kV
Application
LV and MV ( 208V - 38 kV
Generator Protective Devices
ANSI Protective Devices
15/25, 27/59, 81 O/U, 32, 40, 50, 51
Utility Protective Devices
ANSI Protective Devices
15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86
Environmental Parameters
Certifications
IBS, CBC, UBC & OSHPD Certified
Control Panel Enclosure
NEMA 1 or NEMA 3R, Freestanding Construction
Operating Temperature
0 degrees to 50 degrees C
Operating Temperature
0 degrees to 50 degrees C
Storage Temperature
-20 degrees C to +60 degrees C
Storage Temperature
-20 degrees C to +60 degrees C
Low Voltage Standards
NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
Medium Voltage Standards
NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110
Medium Voltage Standards
NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110
  • Generator Demand Priority Control
    • Automatically match the on-line generator capacity to the loads, and avoid unnecessary operation of generator sets.
  • Data Table Interface
    • Accommodates interface with a building management system for monitoring all system parameters via Modbus RTU or TCP
  • Supplemental Hardware Synchronization check relay (ANSI 25 Device)
    • Provides additional discrete synchronization protection
  • Remote Power Monitoring System
    • To monitor breaker status, alarms, metering and other operating parameters