Diesel Generator Sets
D100 GC Generator Set
-
Maximum Rating100 ekW
-
Minimum Rating100 ekW
-
EmissionsU.S. EPA Cert., Tier 3
-
Voltage208 to 600 Volts
Generator Set Specifications
- Maximum Rating
- 100 ekW
- Minimum Rating
- 100 ekW
- Emissions
- U.S. EPA Cert., Tier 3
- Voltage
- 208 to 600 Volts
- Frequency
- 60 Hz
- Speed
- 1800 rpm
- Duty Cycle
- Standby
Engine Specifications
- Engine Model
- C4.4, In-line 4, 4-cycle diesel
- Bore
- 4.1 in
- Stroke
- 5 in
- Displacement
- 269 in³
- Compression Ratio
- 16.7:1
- Aspiration
- Turbocharged
- Fuel System
- Common Rail
- Governor Type
- Mechanical, ADEM™A4
Generator Set Dimensions
- Length
- 82.6 in
- Width
- 43.3 in
- Height
- 52.9 in
- Dry Weight
- 2222 lb
-
Air Inlet System
- Air cleaner; light duty with disposable element
- Air cleaner
-
Cooling System
- Coolant drain line with valve
- Radiator and cooling fan with guards
- Caterpillar extended life coolant
- Fan drive, battery charging alternator drive
-
Control Panel
- GCCP 1.2 Control panel
-
Exhaust System
- Stub pipe, gaskets, raincap and SAE exhaust flange for customer use - shipped loose
-
Fuel System
- Standard open set fuel tank/base supplied base, formed steel with single wall integral 24-hour fuel tank
-
Generator
- Circuit breaker, IEC, 3 pole, mounted in tower panel
- IP23 Protection
- Tower panel, IP22, bottom cable entry
- 12 Leads
- Voltage regulator (single phase sensing)
- Segregated low voltage (AC/DC) wiring panel
-
Governing System
- Mechanical and electrical governing system - model dependent
-
Lube System
- Lubricating oil
- Oil drain line with valve
-
Mounting System
- Termination points for coolant and lube oil drain lines
- Captive linear vibration isolators between base and engine-generator
- Includes lifting provision and drag points
-
Starting/Charging System
- Batteries
- 24V battery with rack and cables
-
General
- Engine and alternator pre-paint, Caterpillar yellow
-
Alternator System
- Anti-condensation heater
- 3 phase sensing
- Permanent magnet excitation (PMG)
- R Frame auxilliary winding
- Quadrature droop kit
-
Circuit breakers
- Circuit breaker upgrades - 4 Pole circuit reaker to 250A, 400A and 630 A
-
Cooling System
- Coolant heater
- Low coolant temperature alarm
- Low coolant level shutdown
-
Control Panel Options
- Earth fault (2 wire only)
- Control panel heater
- GCCP 1.2 Control panel
- Volt free contacts
- Emergency stop with key
- Voltage adjust potentiometer
- Overload shutdown via breaker
- Panel mounted audible alarm
- Battery charger
- Earth leakage (2 wire only)
- Speed adjust potentiometer
-
Enclosures
- Sound attenuated Level 2 enclosure
-
Fuel System
- Low fuel level alarm
- Bunded fuel tank
- Low fuel level shutdown
- High fuel level alarm
-
Mounting Options
- Battery removal
- Electronic governor
- Industrial silencer
- External single point lift - enclosure
- Silencer installation kit
-
Special Packing/Inspectons for Shipment
- PGS Test report @ 0.8 power factor
- PGS Test report @ 1.0 power factor
-
General - Accessories / Miscellaneous
- Packing case - canopied set
- Packing case - compact set
- Stone guards/rad trans flange