Piscataway Campus
732-885-5555
Bensalem Campus
877-726-7663

Electric Power

Engine Paralleling and Integration Control (EPIC)

  • Configuration
    Remote modular paralleling control system (Master Control Panel for the first 2 gensets, separate add-on control panels for up 8 more gensets, and optional control panel for 1 utility breaker)
  • Configuration
    Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control)
  • Modes of Operation
    Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel)
  • Modes of Operation
    Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel)
Technical Summary
Configuration
Remote modular paralleling control system (Master Control Panel for the first 2 gensets, separate add-on control panels for up 8 more gensets, and optional control panel for 1 utility breaker)
Configuration
Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control)
Modes of Operation
Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel)
Modes of Operation
Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel)
Application
LV and MV (208V-27kV)
Application
LV and MV (208V-27kV)
Generator Protective Devices
ANSI Protective Devices
15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade)
Utility Protective Devices
ANSI Protective Devices
15/25. 27/59, 81 O/U, 32,47 (Industrial Grade)
Environmental Parameters
Certifications
UL / cUL 508A
Control Panel Enclosure
NEMA 12
Operating Temperature
0°C to 55°C
Operating Temperature
0°C to 55°C
Storage Temperature
-20°C to 60°C
Storage Temperature
-20°C to 60°C
  • Instant Auto Selector Switch
    • Allows user to return sysem to automatic in the event of a touchscreen failure
  • Generator Control Panel (for 3-10 gensets)
    • With breaker position indications and circuit breaker control switch
  • Utility Control Panel (for utility paralleling and control)
    • With utility close lockout switch, breaker position indications, and circuit breaker control switch
  • Supplemental Hardware 25 Device
    • Provides additional discrete synchronization protection
  • Data Table Interface
    • Accommodates interface with a building management system
  • Generator Demand Priority Control
    • An automatic priority sequencing function to modulate the number of gensets online to control load percentages per machine, assist with fuel efficiency, and maintain adequate reserve capacity