ATS ATC Breaker / Contactor
ATC Power Breaker Bypass Isolation Open/Closed Transition Automatic Transfer Switch
-
Rating Range200-5000A
-
Rating Range200-5000A
-
Transfer TypeBypass isolation, Closed transition
-
Transfer TypeBypass isolation, Closed transition
Technical Summary
- Rating Range
- 200-5000A
- Rating Range
- 200-5000A
- Transfer Type
- Bypass isolation, Closed transition
- Transfer Type
- Bypass isolation, Closed transition
- Switch Type
- Power Breaker
- Switch Type
- Power Breaker
Ratings
- Control Power
-
200-5000A, 2-, 3-, 4-pole
100% rated Short - System Voltage Application
- 120-600 Vac 50/60 Hz
- Time Withstand
- 85,000 for 30 cycles
- Withstand
- 100 kAIC at 600V, 3 cycles
- Applicable Testing
-
CSA C22.2 No. 178 certified
UL 1008 listed up to 3200A
4000A, and 5000A UL 891 listed
-
Controls and Wiring
- All controls relays and industrial grade relays are totally encapsulated to minimize exposure to dust and dirt. Lugs are 90º rated and all control wire is #16 AWG, type XLPE with a 125º temperature rating.
-
Enclosure
- Durable powder-coated steel NEMA 1, 3R or 12 enclosures with three door hinges to ensure proper support of the door and door mounted devices. The hinges have removable hinge pins to facilitate door removal for easy wall mounting or service and are supplied with pad-lockable latches.
-
Available Options
- Surge suppression
- Field selectable, multi ratio, control voltage transformer 50/60 Hz
- Integrated service entrance
- Space heaters
- Remote communications
- Multi-meter options available
- 2- or 4-position test switch
- Selectable automatic or non-automatic operation
- Open or closed transition
- Load sequencing contacts
- Integral overcurrent protection
- Seismic Zone 4 Qualified (BOCA, CBC, IBC, UBC and OSHPD)
-
Optional Delayed Transition includes:
- Pre-transfer signal with 1 N.O. and 1 N.C. contacts
- Time delay neutral
- In-phase transition