ATS MX Contactor
MX150 Microprocessor Controller
-
Rating RangeSwitch Dependent
-
Transfer TypeApplication Dependent
-
Switch TypeApplication Dependent
-
Undervoltage Dropout for Source 1 and Source 275-98% of nominal
Technical Summary
- Rating Range
- Switch Dependent
- Transfer Type
- Application Dependent
- Switch Type
- Application Dependent
Controller Specifications
- Undervoltage Dropout for Source 1 and Source 2
- 75-98% of nominal
- Undervoltage Restore for Source 1 and Source 2
- 85-100% of nominal
- Underfrequency Dropout for Source 1 and Source 2
- 88-98% of nominal
- Underfrequency Restore for Source 1 and Source 2
- 90-100% of nominal
- Delay for Engine Cool Down
- 0-10 seconds
- Delay Transfer to Nonpreferred Source
- 0-5 minutes
- Delay NeutralTransition Time Delays
- 0-10 minutes
- Storage Temperature
- (-30˚C - 75˚C ), -22˚F - 167˚F
- Operating Temperature Ambient
-
40 - 400 amp molded shell (-20˚C to 65˚C) , -4˚F to 149˚F
40 - 4000 amp all others (-20˚C to 60˚C), -4˚F to 149˚F