Diesel Generator Sets
3412C | 900 kVA 50Hz Generator Set
-
Maximum Rating680 kVA
-
Minimum Rating680 kVA
-
EmissionsLow Fuel Consumption
-
Voltage380 to 415 Volts
Generator Set Specifications
- Maximum Rating
- 680 kVA
- Minimum Rating
- 680 kVA
- Emissions
- Low Fuel Consumption
- Voltage
- 380 to 415 Volts
- Frequency
- 50 Hz
- Speed
- 1500 rpm
- Duty Cycle
- Standby, Prime
Engine Specifications
- Engine Model
- 3412C TA, V-12, 4-Stroke Water-Cooled Diesel
- Bore
- 5.4 in
- Stroke
- 6 in
- Displacement
- 1648.86 in³
- Compression Ratio
- 13:01
- Aspiration
- Turbocharged, Air to Air Aftercooled
- Fuel System
- Pump and Lines
- Governor Type
- ADEM™ A5
Generator Set Dimensions
- Length
- 162.4 in
- Width
- 75 in
- Width
- 78.3 in
- Height
- 75 in
- Dry Weight
- 12039 lb
- Dry Weight
- 13030 lb
-
Air Inlet System
- Air cleaner, single element canister type with service indicator
-
Control Panel
- GCCP Control panel
- Emergency stop pushbutton
- Overspeed
- Text alarm/event descriptions
- Low coolant temperature
- Frequency (Hz)
- Overcurrent (50 / 51)
- 4 programmable relay outputs (Form A)
- Volts (L-L & L-N)
- Programmable protective relaying functions:
- Warning/shutdownn with common LED indication of shutdowns for:
- 24 Volt DC operation
- Over/under voltage (27 / 59)
- Engine cycle crank
- Over/under frequency (81 o/u)
- Remote CAN annunciator
- Remote Serial annunciator
- kW (per phase, average & percent)
- Digital I/O module
- Failure to start (overcrank)
- Low oil pressure
- Low coolant level
- Run/auto/ stop/control
- 6 programmable digital inputs
- Accessory module data link
- Features include:
- Compatible with the following optional modules:
- Serial annunciator module data link
- kVA (per phase, average & percent)
- Voltage adjust
- RPM
- Generator temperature monitoring module
- kVAr (per phase, average & percent)
- 2 Programmable relay outputs (Form C)
- DC volts
- Communications
- Local annunciator
- Power factor (per phase & average)
- Speed adjust
- Emergency stop
- Reverse power (kW) (32)
- coolant temperature
- Digital indication for:
- Reverse reactive power (kVAr) (32RV)
- Customer data link (Modbus RTU)
- kW-hr (total)
- Amps (per phase & average)
- High coolant temperature
- Generator phase sequence
- Oil pressure (psi, kPa or bar)
- Operating hours
- 2 Programmable digital outputs
- Environmental sealed front face
-
Cooling System
- Fan and belt guards
- Radiator with guard (Sized for 50 degrees C)
- Coolant drain line with valve, piped to edge of base
- Coolant level shutdown
- Caterpillar extended life coolant
-
Exhaust System
- Stainless steel exhaust flex with ANSI style outlet flange, gasket, bolts and mating weld flange, shipped loose
-
Fuel System
- Primary and Secondary fuel filters
- Water seperator
- Flexible fuel lines terminated on base
- Fuel priming pump
-
Generator and Attachments
- 3-phase sensing
- Busbar termination
- SR4B self excited
- 2:1 Volts/Hz
- Class F temperature rise
- 12 Leads
- Class H insulation
- Reactive droop
- VR6 voltage regulator
-
Governing System
- Cat electronic governor
-
Lube System
- Oil drain line with valve, piped to edge of base
- Oil filter
- Fumes disposal, piped to front of radiator
- Lubricating oil
-
Mounting System
- Base, formed steel with linear vibration isolators between base and engine-generator
-
Starting / Charging System
- Fuel shutoff solenoid
- 45 amp Charging alternator
- Battery with rack, cables
- 24 volt starting motor
-
Air Inlet System
- Dual element air cleaners
- Heavy duty air cleaners
- Open element air cleaners
-
Circuit breakers
- 1250, 1600 Amp, 3 pole, IEC 100% rated, 24 volt DC shunt trip
- 1600 Amp, 3 pole, Non-UL, 100% rated, 24 volt DC shunt trip
-
Control Panel
- Ground fault relay
- Vandal proof panel door
- First local annunicators
- Common alarm/shutdown relay
- Remote custom annunicator
- GCCP Control panel
- Generator running VFC
- GCCP Control panel
- Local discrete I/O package
- Generator temperature monitoring package
-
Cooling System
- Radiator duct flange
- Jacket water heaters
-
European Certifications
- Eurasian Conformity (EAC) mark
-
Exhaust System
- Manifold and turbocharger guards
- Through wall installation kit
- Elbow kit
- Mufflers
-
Generator and Attachments
- Permanent magnet excitation (PMG)
- Space heater
- Digital voltage regulator
- Oversize and premium generators
-
Lube System
- Manual sump pump
-
Mounting System
- Fuel tank base (1200 ltr)
-
Special Tests / Reports
- PGS Test report @ 0.8 power factor
- PGS Test report @ 1.0 power factor
-
Starting / Charging
- Battery disconnect switch
- Heavy duty starting system
- Battery chargers
- Oversize batteries
-
Governing System
- Electronic load share