Piscataway Campus
732-885-5555
Bensalem Campus
877-726-7663

Diesel Generator Sets

3512B Diesel Generator Set

  • Standby Rating
    1500/1400 kW
  • Prime Power Rating
    1360/1275 kW
  • Emissions
    Low Fuel, Low Emissions
  • Voltage
    380 to 480 Volts
Generator Set Specifications
Standby Rating
1500/1400 kW
Prime Power Rating
1360/1275 kW
Emissions
Low Fuel, Low Emissions
Voltage
380 to 480 Volts
Frequency
60 Hz
Speed
1800 rpm
Duty Cycle
Standby, Mission Critical, Prime, Continuous
Maximum Rating
1500 kW
Minimum Rating
1230 kW
Engine Specifications
Engine Model
3512B TA, V-12, 4-Stroke Water-Cooled Diesel
Bore
6.69 in
Stroke
7.48 in
Displacement
51.8 in³
Compression Ratio
14.0:1 Std 15.5:1 HD
Aspiration
TA
Fuel System
Electronic Unit Injection
Governor Type
ADEM™ A3
Generator Set Dimensions
Length
207.8 in
Width
90 in
Height
94.9 in
Dry Weight
24297 lb
Dry Weight
24959 lb
  • Air Inlet System
    • Air cleaner; single element canister type with service indicator
  • Control System
    • True RMS AC metering, 3-phase, +/-2% accuracy
  • Control Panel
    • DC volts
    • 24 Volt DC operation
    • kVA (per phase, average & percent)
    • Engine cool-down timer
    • Coolant temperature
    • kW-hr (total)
    • Amps (per phase & average)
    • Over/under frequency (81 o/u)
    • Text alarm/event descriptions
    • Accessory module data link
    • Alarm acknowledge
    • Warning/shutdown with common LED indication of shutdowns for:
    • Auto/start/stop control
    • Controls:
    • Failure to start (overcrank)
    • Generator mounted - rear facing
    • kVAr (per phase, average & percent)
    • kVAr-hr (total)
    • Reverse reactive power (kVAr) (32RV)
    • Volts (L-L & L-N)
    • Serial annunciator module data link
    • 4 programmable relay outputs (Form A)
    • Lamp test
    • Operating hours
    • Overcurrent (50/51)
    • kW (per phase, average & percent)
    • Communications:
    • 6 programmable digital inputs
    • RPM
    • Engine cycle crank
    • 2 Programmable relay outputs (Form C)
    • IVR includes reactive droop capability, 3-phase voltage sensing
    • High coolant temperature
    • Digital indication for:
    • Environmental sealed front face
    • Power factor (per phase & average)
    • Speed adjust
    • Emergency stop pushbutton
    • Limiter and exciter diode monitor
    • Low oil pressure
    • EMCP 4.2B
    • Low coolant level
    • 2 Programmable digital outputs
    • KVAR/PF modes, RFI suppression, min/max exciter
    • Oil pressure (psi, kPa or bar)
    • Customer data link (Modbus RTU)
    • True RMS AC metering, 3-phase, +/-2% accuracy
    • Overspeed
    • Frequency (Hz)
    • Emergency stop
    • Generator set packages include Caterpillar's voltage regulator (IVR)
    • Reverse power (kW) (32)
    • Low coolant temperature
    • Generator phase sequence
    • Programmable protective relaying functions:
    • Over/under voltage (27/59)
  • Cooling System
    • Caterpillar extended life coolant. (Not included with packages without radiator, installed SF44CTS, shipped loose radiators or heat exchangers)
    • Fan and belt guards
    • JWAC
    • Coolant drain line with valve
    • Coolant level sensors (Not included with packages without radiator)
  • Exhaust
    • Dry exhaust manifold
    • Flanged faced outlet(s)
  • Fuel System
    • Fuel cooler; not included with packages without radiator
    • Fuel priming pump
    • Secondary fuel filters
    • Flexible fuel lines - shipped loose
  • Generators and Attachments
    • NEMA Class H insulation
    • Winding temperature detectors
    • Internal excitation (IE) or Permanent magnet excitation (PMG)
    • LV
    • 6 Lead
    • 60 Hz models: NEMA standard hole pattern
    • Class H temperature rise at 40C ambient (125C prime / 150C standby)
    • 3 Phase brushless, Salient pole
    • Busbar connections, top center mounted, top cable entry
    • Random wound
  • Governing System
    • Woodward 2301A isochronous governor
  • Lube System
    • Oil drain lines and valve
    • Lubricating oil
    • Integral lube Oil cooler
    • Fumes disposal
    • Gear type lube oil pump
    • Oil filter, filler and dipstick
  • Mounting System
    • Rails - engine/generator/radiator mounting
    • Rubber anti-vibration mounts - shipped loose
  • Starting / Charging System
    • Battery disconnect switch
    • Battery and battery rack w/cables
    • 24-Volt electric starting motor
    • 50 Amp Charging alternator
  • General
    • SAE standard rotation
    • Paint - Caterpillar yellow with high gloss black rails & radiator
    • Flywheel and Flywheel housing-SAE No. 00
    • RH service
  • Air Inlet System
    • Air cleaner: Includes installed single element Cat filter and service indicator
    • Dual element air filters
    • Single stage air cleaners
  • Control Panels
    • Cat connect (must choose one)
    • RTD module - may select one
    • Modbus monitoring of packages
    • First local annunicator
    • EMCP 4.3, EMCP 4.4
    • CAN2 network equipment
    • Remote custom annunciator
    • Locale discrete I / O package
    • Vandle proof panel door
  • Cooling System
    • Optional radiator arrangements
    • Water level gauge
    • Coolant
  • Control System
    • Generator temperature monitoring
  • Exhaust System
    • Exhaust Y Adapters
    • Exhaust elbows
    • Mufflers
    • Flexible fittings
    • Exhaust flange and expanders
  • Generators and Attachments
    • Space heater control
    • Generator conversion
    • Space heater
  • Instrumentation
    • Pyrometer and thermocouples
  • Lube System
    • Oil level regulator
    • Prelube manual sump pump
    • Electric prelube sump pump
    • Lube oil
  • Special Tests / Reports
    • PGS Test report @ 0.8 power factor
    • Generator test report
    • Standard generator TVA report
    • PGS Test report @ 0.8 power factor
    • Custom generator TVA report
    • Torsional vibration analysis
    • PGS Test report @ 1.0 power factor
    • Standard engine test charge
    • Generator test report
    • Standard engine test charge
    • PGS Test report @ 1.0 power factor
    • Generator fuel consumption test
  • General
    • Barring devices
  • Crankcase System
    • Ventilation system
    • Protection systems
  • Batteries and Battery Housing
    • 24 Volt battery set - Dry
    • Battery chargers - 10, 20 and 35 amp
  • Power Connection System
    • EMCP voltage and current sensing groups
    • Breaker power connections
    • Center post busbars
  • Circuit breaker - LV Packages
    • Right hand power connections
    • Electronically operated circuit breakers
  • Mounting System
    • Low efficiency isolators
    • Spring type vibration isolators
    • Spring type vibration isolators
    • Low efficiency isolators puck
  • Power Connections
    • Low voltage - Package mounted circuit breakers
    • Low voltage - 1400 and 1600 Frame generators
    • Electrically operated circuit breakers
    • Low voltage - Power connection options
  • Starting / Charging System
    • Jacket water heater wiring groups
    • 35 Amp Battery charger
    • 20 Amp Battery charger
    • Jacket water heaters
    • 10 Amp Battery charger
    • Electric starting motors
    • Starter cover
    • Batteries, racks and cables
  • Starting / Charging Systems
    • Electric starting motors
    • Starter cover
    • Jacket water heater
  • Extended Service Coverage
    • Gold - 36,48, 60, 120 month coverage
    • Cat branded commercial power system
    • Silver - 36 ,48, 60, 120 month coverage
    • Platinum - 24, 36, 48, 60, 120 month coverage