Diesel Generator Sets
3516 Diesel Generator Set
-
Standby Rating1750 ekW
-
Prime Power Rating1600 ekW
-
EmissionsLow Fuel, Low Emissions
-
Voltage380 to 13800 Volts
Generator Set Specifications
- Standby Rating
- 1750 ekW
- Prime Power Rating
- 1600 ekW
- Emissions
- Low Fuel, Low Emissions
- Voltage
- 380 to 13800 Volts
- Frequency
- 60 Hz
- Speed
- 1800 rpm
- Duty Cycle
- Standby, Mission Critical, Prime, Continuous
- Maximum Rating
- 1750 ekW
- Minimum Rating
- 1450 ekW
Engine Specifications
- Engine Model
- 3516 TA, V-16, 4-Stroke Water-Cooled Diesel
- Bore
- 6.69 in
- Stroke
- 7.48 in
- Displacement
- 4210.64 in³
- Compression Ratio
- 13.0:1
- Aspiration
- TA
- Fuel System
- Mechanical unit injection
- Governor Type
- Woodward
- Air Inlet
- Single element canister style with service indicator
- Exhaust Flange Size
- 203.2 mm (8.0 in)
Generator Set Dimensions
- Length
- 247 in
- Width
- 90 in
- Height
- 94.9 in
- Dry Weight
- 28840 lb
-
Air Inlet System
- Air cleaner; single element canister type
-
Control Panels
- Accessory module data link
- Low coolant level
- Environmental sealed front face
- EMCP 4.2B
- 6 Customer programmable digital inputs
- Communications:
- Load histogram feature
- Overspeed
- Alarm acknowledge
- kW-hr (total)
- 24 Volt DC operation
- Over/under voltage (27/59)
- 1 programmable relay outputs (Form C)
- kVAr-hr (total)
- Emergency stop pushbutton
- PLC functionality
- Speed adjust
- Lamp test
- Auto/start/stop control
- Over/under frequency (81 o/u)
- Generator phase sequence
- Revers Power (kW) (32)
- Oil pressure (psi, kPa or bar
- Coolant temperature
- RPM
- Overcurrent (50/51)
- IVR includes reactive droop capability, 3-phase voltage sensing, KVAR / PF modes, RFI suppression, min / max exciter. Limiter and exciter diode monitor
- Controls:
- Number of I/O varies on options selected
- Power factor (per phase & average)
- 0 True RMS AC metering, 3-phase, +/-2% accuracy
- kVA (per phase, average & percent)
- Serial annunciator module data link
- Customizable screens
- Generator mounted - rear facing
- kW (per phase, average & percent)
- Text alarm/event descriptions
- DC volts
- Low oil pressure
- Controls: Speed adjust - Auto/start/stop control - Engine cool-down timer - Engine cycle crank - Alarm acknowledge - Lamp test - Load histogram feature - PLC functionality - Customizable screens -0 True RMS AC metering, 3-phase, +/-2% accuracy
- Reverse reactive power (kVAr) (32RV
- Frequency (Hz)
- Low coolant temperature
- 3 Analog inputs
- Cat connect
- kVAr (per phase, average & percent)
- Warning/shutdown with common LED indication of shutdowns for:
- Engine cycle crank
- Failure to start (overcrank)
- Programmable protective relaying functions:
- Emergency stop
- Customer data link (Modbus RTU
- Engine cool-down timer
- Volts (L-L & L-N)
- Amps (per phase & average)
- Operating hours
- High coolant temperature
- Digital indication for:
- 1 programmable digital outputs
- 4 programmable relay outputs (Form A)
-
Cooling System
- Certified standard PGS provided
-
Exhaust System
- Flanged faced outlet(s)
- Dry exhaust manifold
-
Fuel System
- Secondary fuel filters
- Fuel cooler; not included with packages without radiator
- Flexible fuel lines - shipped loose
- Fuel priming pump
-
General
- Right hand servicing
- Flywheel and flywheel housing - SAE No. 00
- SAE standard rotation
-
Generator and Attachments
- NEMA Class H insulation system, Class H temperature rise at 40C ambient (125C prime/150C standby)
- NEMA Class H insulation system, Class H temperature rise at 40C ambient (125C prime/150C standby)
- Winding temperature detectors
- Winding temperature detectors
- Permanent magnet excitation (PMG)
- Class H insulation, Class F temperature rise at 40C ambient (105C prime/130C standby)
- Six lead
- Permanent magnet excitation (PMG)
- Internal excitation (IE)
- 3 Phase brushless, Salient pole
- Winding temperature detectors
- Medium voltage:
- Random wound
- Anti-condensation space heater
- Low voltage:
- High voltage:
- Busbar connections, top center mounted, top cable entry
- Form wound
- Busbar connections, right side extension box, bottom cable entry
- Form wound
- NEMA standard hole pattern
- NEMA standard hole pattern
-
Governing System
- ADEM A3
-
Literature
- Parts book
-
Lubrication System
- Fumes disposal
- Lubricating oil
- Gear type lube oil pump
- Oil filter, filler and dipstick
- Oil drain lines and valve
- Integral lube oil cool
-
Mounting System
- Rails - engine/generator/radiator mounting
- Anti-vibration mounts (shipped loose)
- Rubber anti-vibration mounts - shipped loose
-
Starting System
- Battery and battery rack w/cables
- 45 Amp Charging alternator
- Battery disconnect switch
- 24 Volt electric starting motor
-
Control System
- Controller: EMCP 4.2B
- Local annunciator module: [ ] NFPA 110 [ ] Custom
-
Air Inlet System
- Dual element air cleaner
- Single element filter
-
Cooling System
- Standard ambient radiators
- Coolant
- Optional installed ATAAC radiators
- Optional installed radiators
- Water level switch gauges
- Standard ambient ATAAC radiators
-
Engine Options
- Starting motors: [ ] Standard [ ] Heavy duty
- Batteries: [ ] Standard (1400 CCA) [ ] Heavy Duty (2800 CCA)
- Starting aids: [ ] 220V 50 Hz Jacket water heater
- Battery charger: [ ] 10A [ ] 20A [ ] 35A
- Air cleaner: [ ] Single element air cleaners [ ] Dual element air cleaners [ ] Heavy duty air cleaners
- Muffler: [ ] Industrial Grade
-
Crankcase System
- No explosion relief valves
- Ventilation system
- Explosion relief valves
-
Alternators
- Temperature rise (over 40°C ambient): [ ] 150°C [ ] 125°C [ ] 105°C [ ] 80°C
-
Exhaust System
- Y Adapters
- Tier 4 clean emissions module
- Tier 4 dosing cabinet
- Elbows
- Tier 4 clean emission MOD Kits
- Exhaust offset
- Flanges
- Flange and exhaust expanders
- Flexible fittings
- Mufflers
- Clean emission parts
-
Fuel System
- Fuel priming pumps (Tier 4) - Manual or electric
- Primary fuel filter
-
General
- US aid emblem
- Special paint (Colors other than Caterpillar yellow or high performance paints)
- The following options are based on regional and product configuration:
- UL 2200 package
- Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
-
Generators and Attachments
- High voltage: 12470, 13200, 13800 volts, 3 phase 1800 rpm,FW, PM, No. of Leads = 6, Pitch = .6667: 2700, 3000 Frame
- Generator conversion
- Low / Medium voltage: 380, 440, 480, 600 volts, 3 phase 1800 rpm. RW, IE, No. of Leads = 6, Pitch = .6667: 1600 Frame
- Thermostat for space heater
- Low / Medium voltage: 380, 416, 440, 480, 600, 2400, 4160 Volts, 3 Phase 1800 RPM, FW, PM, No. of Leads = 6, Pitch = .6667: 1600, 1800 Frame
- Alternator air cleaner
- Differential current transformers (DCT)
- High voltage: 6300, 6600, 6900 volts, 3 phase 1800 rpm, FW, PM, No. of Leads = 6, Pitch = .6667: 2700, 3000 Frame
- Differential current transformers (DCT) 8.7 kV and 15 kV classes
- Space heater kit
-
Power Termination
- Circuit breaker operation: [ ] Electrical
- Circuit breaker rating: [ ] 2000A [ ] 2500A [ ] 3200A [ ] 4000A
- Circuit breaker trip unit: [ ] LSI [ ] LSIG [ ] LSIG-P
- Power termination: [ ] Busbar [ ] Circuit breaker
-
Extended Service Contract (ESC)
- Extended Service Contract (ESC): [ ] 2 Year [ ] 3 Year [ ] 5 Year
-
Instrumentation
- Pyrometer and Thermocouples
-
Lubrication System
- Lube oil in standard sump
- Prelube pumps
- Oil level regulator
-
Mounting System
- Puck style low efficiency isolators
- Spring type vibration isolators
- IBC vibration isolators
-
Power Connections
- Ground cables between generator and terminal box
- Neutral ground connections
- 2700 Frame, four lead, four terminal
- Rear power connections
- Right side power connections
- Left side power connections
- Low voltage Circuit breakers
- Center post busbars
-
Special Tests / Reports
- Generator test report
- OSHPD Certification
- Canadian Standards Association certification
- PGS Test report @ 1.0 power factor
- IBC Certification
- Fuel consumption test
- Generator set fuel consumption test
- PGS Test report @ 0.8 power factor
- Standard engine test charge
- Torsional vibration analysis reports
-
Starting and Charging
- Electric starting motors
- Air pressure regulator
- Starter cover
- Air starting motors
- 24 Volt battery set - Dry
- 10, 20, 35 and 50 Amp Battery chargers
- Jacket water heaters
- Engine barring device
-
Extended Service Coverage
- Platinum, Gold and Silver coverage