Diesel Generator Sets
3516E Generator Set
-
Standby Rating3500/3250/3000 kVA
-
Prime Power Rating3175/2950/2725 kVA
-
EmissionsU.S. EPA Cert. Tier 2 / Low NOx
-
Voltage380 to 11000 volts
Generator Set Specifications
- Standby Rating
- 3500/3250/3000 kVA
- Prime Power Rating
- 3175/2950/2725 kVA
- Emissions
- U.S. EPA Cert. Tier 2 / Low NOx
- Voltage
- 380 to 11000 volts
- Frequency
- 50 Hz
- Speed
- 1500 rpm
- Duty Cycle
- Standby, Mission Critical, Prime
- Maximum Rating
- 3500 kVA
- Minimum Rating
- 2725 kVA
Engine Specifications
- Engine Model
- 3516E, V-16, 4-Stroke Water-Cooled Diesel
- Bore
- 6.69 in
- Stroke
- 8.46 in
- Displacement
- 4765 in³
- Compression Ratio
- 14.0:1
- Aspiration
- ATAAC
- Fuel System
- Electronic Unit Injection
- Governor Type
- Adem™ A5
Generator Set Dimensions
- Length
- 302.6 in
- Length
- 306.5 in
- Width
- 102.8 in
- Height
- 131.6 in
- Dry Weight
- 44930 lb
- Dry Weight
- 45651 lb
-
Air Inlet System
- Air cleaner; single element canister type
-
Control System
- Generator set packages include:
- Emergency stop pushbutton
- 24 Volt DC operation
- KVAR / PF modes
- IVR includes reactive droop capability
- Cat ECS 100
- Text alarm/event descriptions
- Generator mounted - rear facing
- Environmental sealed front face
- RFI suppression
- 3 Phase voltage sensing
- Caterpillar's voltage regulator
- Min / max exciter
- Limiter and exciter diode monitor
- Controls:
- Speed adjust
- Auto/start/stop control
- Engine cycle crank
- Engine cool
- Alarm acknowledge
- PLC functionality
- Customizable screens
- Lamp test
- Load histogram feature
- Generator phase sequence
- 1 Programmable relay outputs (Form C)
- RPM
- High coolant temperature
- Accessory module data link
- Low coolant level
- Number of I/O varies on options selected
- Digital indication for:
- Reverse power (kW) (32)
- Reverse reactive power (kVAr) (32RV)
- Overcurrent (50/51)
- 6 Customer programmable digital inputs
- 3 Analog inputs
- Serial annunciator module data link
- Over/under frequency (81 o/u)
- Low coolant temperature
- +/- 2% accuracy
- Programmable protective relaying functions:
- Failure to start (overcrank)
- 4 Programmable relay outputs (Form A)
- Cat connect
- Over/under voltage (27/59)
- 1 Programmable digital outputs
- 0 True RMS AC metering
- 3 Phase
- Communications:
- Overspeed
- DC volts
- Operating hours
- Coolant temperature
- Oil pressure (psi, kPa or bar)
- Volts (L-L & L-N)
- Power factor (per phase & average)
- Frequency (Hz)
- Amps (per phase & average)
- kW (per phase, average & percent)
- kVA (per phase, average & percent)
- kVAr (per phase, average & percent)
- Low oil pressure
- kVAr-hr (total)
- kW-hr (total)
- Warning/shutdown with common LED indication of shutdowns for: Low oil pressure - High coolant temperature - Overspeed - Emergency stop - Failure to start (overcrank) - Low coolant temperature - Low coolant level -
-
Cooling System
- ATAAC - 3516E package radiators shipped installed
- Certified standard PGS provided
-
Exhaust System
- Dry exhaust manifold
- Flanged faced outlet(s)
-
Fuel System
- Fuel cooler; not included with packages without radiator
- Secondary fuel filters
- Flexible fuel lines - shipped loose
-
General
- SAE standard rotation
- Flywheel and flywheel housing - SAE No. 00
- Right hand servicing
- Caterpillar yellow with high gloss black rails and radiator
-
Generator and Attachments
- Anti-condensation space heater
- Low voltage: Random wound - Internal excitation (IE) - Winding temperature detectors - NEMA Class H insulation system, Class H temperature rise at 40C ambient (125C prime/150C standby) - Busbar connections, top center mounted, top cable entry - NEMA standard hole pattern
- 3 Phase brushless, Salient pole
- NEMA Class H insulation system, Class H temperature rise at 40C ambient (125C prime/150C standby)
- Winding temperature detectors
- High voltage:
- Medium voltage:
- Class H insulation, Class F temperature rise at 40C ambient (105C prime / 130C standby)
- NEMA standard hole pattern
- 6 Lead
- Permanent magnet excitation (PMG)
- Form wound
- Busbar connections, right side extension box, bottom cable entry
-
Governing System
- ADEM A5
-
Literature
- Parts book
- Operation & Maintenance Manual
-
Lubrication System
- Gear type lube oil pump
- Lubricating oil
- Oil filter, filler and dipstick
- Integral lube oil cool
- Oil drain lines and valve
- Fumes disposal
-
Mounting System
- Rails - Engine/generator/radiator mounting
- Anti-vibration mounts (shipped loose)
- Rubber anti-vibration mounts - shipped loose
-
Starting System
- 24 Volt electric starting motor
- 45 Amp Charging alternator
- Battery and battery rack w/cables
- Battery disconnect switch
-
Control System
- EMCP 4.4
-
Air Inlet System
- Single element filter
- Dual element air cleaner
-
Cooling System
- Standard ambient ATAAC radiators
- Water level switch gauges
- Optional installed ATAAC radiators
- Coolant
- Optional installed radiators
- Standard ambient radiators
-
Crankcase System
- Ventilation system
- Explosion relief valves
- No explosion relief valves
-
Exhaust System
- Y Adapters
-
Fuel System
- Primary fuel filter
- Fuel priming pumps (Tier 4) - Manual or electric
-
General
- US aid emblem
- Special paint (Colors other than Caterpillar yellow or high performance paints)
-
Generators and Attachments
- Thermostat for space heater
- Alternator air cleaner
- Differential current transformers (DCT) 8.7 kV and 15 kV classes
- Generator conversion
- Space heater
- Low / Medium voltage: 380/400/415 volts, 3 phase 1500 rpm. RW, PM, No. of Leads = 6, Pitch = .6667: 1600 and 1800 Frames
- Low / Medium voltage: 380/400/415 volts, 3 phase 1500 rpm. RW, IE, No. of Leads = 6, Pitch = .6667: 1600 Frame
-
Instrumentation
- Pyrometer and thermocouples
-
Lubrication System
- Lube oil in standard sump
- Prelube pumps
- Oil level regulator
-
Mounting System
- Puck style low efficiency isolators
- Spring type vibration isolators
- IBC vibration isolators
-
Power Connections
- Neutral ground connections
- Center post busbars
- Right side power connections
-
Special Tests / Reports
- Generator set fuel consumption test
- Torsional vibration analysis reports
- PGS Test report @ 0.8 power factor
- IBC Certification
- PGS Test report @ 1.0 power factor
- Canadian Standards Association certification
- Standard engine test charge
- Generator test report
- Fuel consumption test
- OSHPD Certification
-
Starting and Charging
- Air pressure regulator
- Jacket water heaters
- Air starting motors
- 24 Volt battery set - Dry
- Starter cover
- Engine barring device
- 10, 20, 35 and 50 Amp Battery chargers
- Electric starting motors
-
Extended Service Coverage
- Platinum, Gold and Silver coverage