Piscataway Campus
732-885-5555
Bensalem Campus
877-726-7663

Diesel Generator Sets

C32 | 1500 kVA 50Hz Generator Set

  • Maximum Rating
    1500 kVA
  • Minimum Rating
    910 kVA
  • Emissions
    Low Fuel, Low Emissions
  • Voltage
    400 to 3300 Volts
Generator Set Specifications
Maximum Rating
1500 kVA
Minimum Rating
910 kVA
Emissions
Low Fuel, Low Emissions
Voltage
400 to 3300 Volts
Frequency
50 Hz
Speed
1500 rpm
Duty Cycle
Standby, Mission Critical, Prime, Continuous
Engine Specifications
Engine Model
C32 TA, V-12, 4-Stroke Water-Cooled Diesel
Bore
5.71 in
Stroke
6.38 in
Displacement
1958.86 in³
Compression Ratio
15.0:1
Aspiration
Turbocharged, Air to Air Aftercooled
Fuel System
MEUI
Governor Type
Adem™A4
Generator Set Dimensions
Length
164 in
Length
176.6 in
Width
66.3 in
Width
87.8 in
Height
85.1 in
Height
86.4 in
Dry Weight
14700 lb
Dry Weight
17855 lb
  • Air Inlet System
    • Single element canister type with service indicator
  • Control Panel
    • GCCP Control panel
    • Warning shutdowns
    • Programmable protective relaying functions
    • Communications
    • Digital indicators
    • Control features
  • Cooling System
    • Radiator fan and fan drive
    • Coolant drain line with valve
    • ATAAC
    • Caterpillar extended life coolant
    • Fan and belt guards
    • Low coolant level sensor
  • Exhaust
    • 203 mm (8 in) ID round flanged outlet
    • Exhaust manifold - dry
  • Fuel System
    • Fuel cooler
    • Secondary fuel filters
    • Primary fuel filter with water separator
    • Fuel priming pump
  • Generators and Attachments
    • Permanent magnet excitation (PMG)
    • Reactive droop
    • Integrated voltage regulator (IVR)
    • 6 Lead
    • Salient pole
    • Class H temperature rise at 40C ambient
    • Busbar connections, top center mounted, top cable entry
    • Internal excitation (IE)
    • 3 Phase brushless
    • Winding temperature detectors
    • IEC standard hole pattern
    • NEMA Class H insulation
  • Governing System
    • ADEM(tm) A4
  • Mounting System
    • Rails - engine/generator/radiator mounting
    • Rubber anti-vibration mounts
  • Lube System
    • Fumes disposal
    • Integral lube Oil cooler
    • Oil filter, filler and dipstick
    • Gear type lube oil pump
    • Lubricating oil
    • Oil drain lines and valve
  • Power Termination
    • Busbar
  • Starting / Charging System
    • Battery disconnect switch
    • 45 Amp Charging alternator
    • 24 Volt electric starting motor
    • Battery, rack and cables
  • General
    • SAE standard rotation
    • RH service
    • Flywheel and flywheel housing-SAE
    • Caterpillar yellow with high gloss black rails & radiator
  • Air Inlet System
    • Standard air cleaners
    • Dual element air cleaner
    • Heavy duty air cleaner
  • Circuit breakers
    • Shrouds
    • Enclosures - Control packaging
    • 1600, 2000, 2500 and 3200 Amp, 3 Pole, IEC-Rated Circuit breakers
    • Cable supports
    • Circuit breaker wiring groups
    • Power connection covers
    • Center posts busbars
    • 800, 1600, 2000, 2500 and 3200 Amp, 4 Pole, IEC rated Circuit breakers
    • 400, 800, 1200, 1600, 2000, 2500 and 3000 Amp, 3 Pole, UL-100% Rated Circuit breakers
  • Control Panels
    • GCCP Control panel
  • Cooling System
    • High ambient radiator
    • Extended life coolant
    • Radiator duct flange
    • Standard radiator
    • Certified radiator
  • Enclosures
    • AC Panel, outlets and lights
    • Premium sound attenuated enclosure
    • Enclosure louvres - fixed and motorized
    • Enclosure fuel tank options
    • Color options
    • Panel bracket
    • Sound attenuated enclosure
    • DC lighting package
    • Cold weather bundle
  • Exhaust System
    • All C32 engines have 203 mm (8 in) exhaust outlets
    • Mufflers
    • Elbow mounting kit
    • Flange and exhaust expanders
    • Flexible fittings
    • Guard and shield system
    • Flanges
    • Exhaust through the wall kit
  • Generator and Attachments
    • Medium voltage generators
    • Low voltage generators
  • Lube System
    • Oil pan
    • Prelube manual sump pump
    • Oil level regulator
  • Mounting System
    • IBC vibration isolators
    • Spring type vibration isolators
    • Standard package isolators
    • Mounting base types
  • Power Termination
    • Circuit breakers, IEC compliant
    • Circuit breakers, UL listed
  • Power Connections
    • Center post busbars
    • Neutral grounding connection
    • Low voltage connection cables
  • Starting / Charging System
    • Electric starting motor - Standard/heavy duty
    • Space heater
    • Standard 24 volt open package battery set - Dry
    • 10 Amp Battery charger
    • 20 Amp Battery charger
    • Jacket water heater
    • 10 Amp enclosure Battery charger
    • 35 Amp Battery charger
  • Special Tests / Reports
    • Standard engine test
    • OSHPD seismic Certifications
    • Generator test report
    • Custom generator TVA report
    • Standard genset Torsional Vibration Analysis (TVA) report
    • IBC seismic Certifications
    • PGS Test report @ 0.8 power factor
    • PGS Test report @ 1.0 power factor
    • CSA test and certification
  • General
    • Special paint
    • US aid emblem