Piscataway Campus
732-885-5555
Bensalem Campus
877-726-7663

Diesel Generator Sets

C9 Generator Set

  • Maximum Rating
    330 kVA
  • Minimum Rating
    230 kVA
  • Emissions
    EU Stage IIIA
  • Voltage
    200 to 400 Volts
Generator Set Specifications
Maximum Rating
330 kVA
Minimum Rating
230 kVA
Emissions
EU Stage IIIA
Voltage
200 to 400 Volts
Frequency
50 Hz
Speed
1500 rpm
Duty Cycle
Standby, Prime
Engine Specifications
Engine Model
C9 ATAAC, I-6, 4-Stroke Water-Cooled Diesel
Bore
4.41 in
Stroke
5.87 in
Displacement
537.01 in³
Compression Ratio
16.1:1
Aspiration
Air to Air Aftercooled
Fuel System
Hydraulic electronic unit injection
Governor Type
Adem™A4
Exhaust Flange Size
127 mm (5.0 in)
Aspiration
Air to Air Aftercooled
Fuel System
Hydraulic electronic unit injection
Bore
4.41 in
Displacement
537.01 in³
Stroke
5.87 in
Generator Set Dimensions
Length
157 in
Width
47.5 in
Height
73.5 in
  • Air Inlet System
    • Air cleaner, light duty with disposable paper filter
  • Control Panels
    • GCCP 1.3
  • Cooling System
    • Fan drive, battery charging alternator drive
    • Radiator and cooling fan with guard
    • Caterpillar extended life coolant
    • Coolant drain line with valve
  • Exhaust System
    • Stainless steel exhaust flex, gaskets, rain cap & SAE exhaust flange for customer use - shipped loose
  • Fuel System
    • Base, formed steel with single wall integral 8-hour fuel tank
    • Standard open set fuel tank/base supplied
  • Generators and Generator Attachments
    • 12 Leads
    • Mandatory option circuit breaker, IEC, 3 pole mounted in power centre
    • Voltage regulator (single phase sensing)
    • Segregated low voltage (AC/DC) wiring panel
    • IP23 Protection
    • Power centre, IP22
  • Governing System
    • Cat electronic governor (ADEM A4)
  • Lube System
    • Oil drain valves
    • Lubricating oil
    • Oil cooler
  • Mounting System
    • Includes lifting provisions and termination points for coolant and lube oil drain lines
    • Captive linear vibration isolators between base and engine-generator
  • Starting / Charging System
    • 24V battery with rack and cables
  • General
    • Engine and alternator re-paint, Caterpillar yellow
  • Certifications
    • European Certificate for Conformance
    • Global Certification for CIS
  • Air inlet system
    • Single element air cleaner
  • Circuit breakers
    • 4 Pole (IEC-100% rated) Circuit breaker upgrades: 400, 630, 800 and 100 amps
  • Control Panels
    • Control panel protective devices: Earth fault relay ; Earth leakage ground fault ; overload shutdown via breaker ; Low fuel level shutdown ; Low fuel level alarm ; Fuel level sensor
    • Control panel Options: Volt free contacts ; Local alarm horn ; Oil temperature displays
  • Cooling System
    • Radiator duct flange
    • Low coolant temperature alarm
  • Enclosures
    • Sound attenuated enclosure
    • High ambient sound attenuated enclosure
  • Exhaust System
    • 5 and 6 inch elbow kits
    • 5 - 6 inch flange adaptor
    • Mufflers - End in/end out; 10 dBA or 25 dBA attenuation
    • 6 inch flange
  • Fuel System
    • Integral dual wall fuel tank base
  • Generators and Attachments
    • Permanent magnet excitation (PMG) generator
    • Oversize, AREP, CIP generators
  • Mounting System
    • Narrow skid base
  • Starting / Charging System
    • Jacket water heater
    • 5 Amp single Battery charger
    • Battery disconnet switch