Diesel Generator Sets
D175 GC Generator Set
-
Maximum Rating175 ekW
-
Minimum Rating175 ekW
-
EmissionsU.S. EPA Cert., Tier 3
-
Voltage208 to 600 Volts
Generator Set Specifications
- Maximum Rating
- 175 ekW
- Minimum Rating
- 175 ekW
- Emissions
- U.S. EPA Cert., Tier 3
- Voltage
- 208 to 600 Volts
- Frequency
- 60 Hz
- Speed
- 1800 rpm
- Duty Cycle
- Standby
Engine Specifications
- Engine Model
- C7.1 I-6, 4-Cycle Diesel
- Bore
- 4.1 in
- Stroke
- 5.31 in
- Displacement
- 427.8 in³
- Compression Ratio
- 16.7:1
- Aspiration
- Turbocharged, Air to Air Aftercooled
- Fuel System
- Electronic, Common Rail
- Governor Type
- ADEM™A4
Generator Set Dimensions
- Length
- 103.7 in
- Width
- 51.2 in
- Height
- 58.7 in
- Dry Weight
- 3741 lb
-
Air Inlet System
- Air cleaner; light duty with disposable element
-
Control Panels
- GCCP 1.2 Control panel
-
Cooling System
- Coolant drain line with valves
- Fan drive, battery charging alternator drive
- Caterpillar extended life coolant
- Radiator and cooling fan with guards
-
Generator and Generator Attachments
- Tower panel, IP22, bottom cable entry
- IP23 Protection
- 12 Leads
- Circuit breaker, IEC, 3 pole, mounted in tower panel
- Segregated low voltage (AC/DC) wiring panel
- Voltage regulator (single phase sensing)
-
Exhaust System
- Stub pipe, gaskets, raincap and SAE exhaust flange for customer use - shipped loose
-
Fuel System
- Base, formed steel with single wall integral 24-hour fuel tank
- Standard open set fuel tank/base supplied
-
Lube System
- Lubricating oil
- Oil drain line with valve
-
Mounting System
- Termination points for coolant and lube oil drain lines
- Includes lifting provision and drag points
- Captive linear vibration isolators between base and engine-generator
-
Starting / Charging System
- 24V battery with rack and cables
-
Governing System
- Mechanical and electrical governing system - model dependent
-
General
- Engine and alternator pre-paint, Caterpillar yellow
-
Alternator System
- Permanent magnet excitation (PMG)
- Quatrature droop king
- Alternator removal
- 3 Phase sensing
- R Frame auxiliary winding: R2273L4 SE aux alt 07, aux alt 08 and aux alt 10
- Anti-condensation heater
- Optional LC Frame alternator with coastal insulation protection
-
Circuit breakers
- Padlockable breaker device
- 4 Pole 250A, 400A and 630A Circuit breakers
-
Control Panel Options
- Earth fault (2 wire only)
- Speed adjust contacts
- Panel mounted audible alarm
- Volt free contacts
- Earth leakage (2 wire only)
- Overload shutdown via breaker
- Control panel heater
- Speed adjust potentiometer
- Battery charger
- Emergency stop with key
-
Control System
- Static battery charger
- Volt free contacts for common alarm
- Volt free contacts for generator set running
- GCCP 1.2
-
Cooling System
- Low coolant temperature
- Coolant heater
- Low coolant level shutdown
-
Enclosures
- Sound attenuated level 2 enclosure
-
Mounting Options
- Electronic governor
- Silencer installation kit
- Industrial silencer removal
- Battery removal
- Residential silencer
-
Fuel Systems
- Low fuel level alarm
- Compact skidbase for open sets
- DEFRA bunded fuel tank
- Open set narrow tankbase
- Low fuel level shutdown
- Skidbase for CALG enclosure sets
- High fuel level alarm
-
Test Reports
- PGS Test report @ 1.0 power factor
- PGS Test report @ 0.8 power factor
-
General
- Stone guards/radiator trans flange
-
Global Certifications
- Certification for CIS
-
Power Termination
- Circuit breaker, IEC, 4 pole
-
Accessories / Miscellaneous
- Packing case - compact set
- Packing case - canopied set