Maximum Rating600 ekW
-
Minimum Rating600 ekW
-
EmissionsNon Regulated
-
Voltage220 to 480 Volts
Generator Set Specifications
- Maximum Rating
- 600 ekW
- Minimum Rating
- 600 ekW
- Emissions
- Non Regulated
- Voltage
- 220 to 480 Volts
- Frequency
- 60 Hz
- Speed
- 1800 RPM
- Duty Cycle
- Standby
Engine Specifications
- Engine Model
- C15 In-line 6, 4-cycle diesel
- Bore
- 5.4 in
- Stroke
- 6.8 in
- Displacement
- 928 in³
- Compression Ratio
- 16.1:1
- Aspiration
- Turbocharged Air-to-Air Aftercooled
- Fuel System
- EUI
- Governor Type
- Adem™A4
Generator Set Dimensions
- Length
- 131 in
- Width
- 60.6 in
- Height
- 86.1 in
- Dry Weight
- 8364 lb
-
Engine
- Cat® C15 Inline 6 cylinder, 4 stroke diesel
-
Air Inlet
- Air cleaner
-
Control Panels
- GCCP 1.1
-
Governor
- Mechanical governor
-
Cooling
- Package mounted radiator
-
Alternator
- A Frame standard alternator
-
Control Panel
- EMCP 4 Genset controller
-
Fuel Storage
- Single wall 8 hour fuel tank
-
Cooling System
- Radiator and cooling fan with guards
- Fan drive, battery charging alternator drive
-
Fuel
- Fuel priming pump
- Primary fuel filter with integral water separator
- Secondary fuel filters
-
Exhaust
- Exhaust flange outlet
-
Electrical Options
- 3 Pole Circuit breaker
- Neutral earth link
- 24 Volt battery with rack and cables
-
Air inlet system
- Air cleaner; light duty with disposable element
-
Lube system
- Lubricating oil
- Oil drain line with valve
-
Generator
- Matched to the performance and output characteristics of Cat engines
- IP23 Protection
- Load adjustment module provides engine relief upon load impact and improves load acceptance and recovery time
-
Mounting system
- Captive linear vibration isolators
- Lifting provision and drag points
-
General
- Engine and alternator pre paint, Caterpillar yellow
- Engine and alternator pre paint, Caterpillar yellow
- Paint - Caterpillar yellow except rails and radiators gloss black
-
Power Termination
- Busbar
-
Generator and Attachments
- Power center, IP22
- Optional LC Frame generator - IP23 Protection
- Mandatory option circuit breaker, IEC, 3 pole, mounted in power centre
- Integrated voltage regulator (IVR)
- Segregated low voltage (AC/DC) wiring panel
-
Mounting
- Rubber vibration isolators
-
Governing System
- Cat electronic governor (ADEM A4).
-
Lube System
- Oil drain valves
- Oil cooler
-
Mounting System
- Captive linear vibration isolators between base and engine-generator includes lifting provisions and termination points for coolant and lube oil drain lines
-
Starting/Charging
- 24 volt starting motor
- Batteries
- 24 Volt battery with rack and cables
-
Exhaust
- Industrial, residential, critical mufflers
-
Control panel
- Speed and Voltage adjust potentiometers
- PLG 4G/3G/Ethernet
- Annunciator
- Emergency E-Stop
-
Enclosure
- Cat GC enclosure
-
Generator
- Oversize and premium generators
- Anti-condensation heater
- Excitation: [ ] Permanent magnet excitation (PMG) Excited (PM) [ ] Internally Excited (IE)
-
Power Termination
- Circuit breakers, UL listed
- Circuit breakers, IEC compliant
-
Electrical Options
- 4 Pole Circuit breaker
- Auxiliary contacts
- Padlockable circuit breaker
- Battery charger
- Wet battery
-
Alternator
- Space heater
- AVR
-
Fuel System
- Dual wall 8 hour fuel tank
- Single wall 8 hour fuel tank with spill containment
- Low fuel level shutdown
- Low and high fuel level alarms
- Manual fuel transfer pump
- Fuel transfer system controls
- Dual wall fuel tank base
-
Starting/Charging
- Jacket water heater
- Heavy duty starting system
- Battery chargers
- Charging alternator
- Oversize batteries
-
Air inlet system
- Single stage air filter
- Dual element air filter
-
Certifications
- EU Certificate of Conformance (CE)
- EAC Certification
-
Extended service coverage
- 3, 4, 5 and 10 Years
-
General
- The following options are based on regional and product configuration:
- Single or dual wall integral fuel tanks
- Narrow, wide or skid base
- Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
- EU Certificate of Conformance (CE)
- CSA Certification
- EEC Declaration of Conformity
- Integral & sub-base UL listed dual wall fuel tanks
- UL 2200 package
- Sound attenuated, weather protective or high ambient weather protective enclosure
- Automatic transfer switches (ATS)
- Single or dual wall sub-base fuel tanks
-
Enclosures
- High ambient sound attenuated enclosures
-
Exhaust System
- Industrial silencer
- 10 dBA Attenuation silencer
- Flexible exhaust fittings
- 6 and 8 inch elbow kit
- End in/end out mufflers - 10, 25 and 35 dBA attenuation
- Engine mounted muffler
- Manifold and turbocharger guards
- 6 and 8 inch flange GP
-
Generator and Attachments
- Oversize A Frame generator
- Permanent magnet excitation (PMG) generator
- Oversize LC frame generator
- Ingress protection
- LC frame generator
- Space heaters
- LC frame CIP generator
- CIP A Frame generator
-
Lube System
- Manual sump pump
-
Mounting System
- Narrow skid base - replaces standard fuel tank base
-
Special Test / Reports
- PGS Test report @ 1.0 power factor
- PGS Test report @ 0.8 power factor
-
Starting / Charging System
- 5 Amp single Battery charger
- Battery disconnect switch
- Jacket water heater