XQC1200

  • Rating
    1150kW (1438 kVA) Continuous
  • Frequency
    50/60 Hz
  • Voltage
    230 - 480 V
  • IPP Overload 50Hz
    1205 ekW (1506 kVA)
Generator Set
Rating
1150kW (1438 kVA) Continuous
Frequency
50/60 Hz
Voltage
230 - 480 V
IPP Overload 50Hz
1205 ekW (1506 kVA)
IPP Overload 60Hz
1330kW; (1662KVA)
IPP Rated 60Hz
1260 ekW (1575 kVA)
Engine
Engine
Cat 3512C
Fuel
Diesel
Dimensions
Height
114 in
Length
240 in
Weight
47440 lb
Width
97.5 in
  • Cat 3512C heavy duty diesel engine
    • Heavy duty, dual element, PowerCore air cleaners with service indicators
    • Secondary fuel filters
    • Full flow oil filters with water-cooled oil cooler. Requires API CI-4 or higher lube oil
    • Lubricating oil system includes make-up system (113-L tank), oil drain lines routed to the engine rail, and quick evacuation system for faster, cleaner oil changes
    • Jacket water heater (9 kW, 3-phase 480VAC) with electric pump
    • Fuel cooler and electric priming pump
    • Electronic differential pressure monitoring of all filters
    • Electronic ADEM A4 engine controls
    • 24V electric starting motor
  • SR5 Generator
    • Double-bearing, SR-5 generator with anti-condensation space heaters (1.2 kW, 480VAC)
    • Brushless, random-wound, permanent magnet excited, thouree-phase, 4-lead design
    • Class H insulation operating at Class F temperature for extended life
    • Cat Integrated Voltage Regulator (Cat IVR)
    • Stator winding and bearing temperature sensors and RTD module
    • Metallic mesh generator air inlet filters (washable) with differential pressure monitoring
    • Coastal Insulation Protection
  • 20' ISO high-cube container, 9-High stackable, CSC certified
    • Hinged, radiator air intake louvers
    • Sound-attenuated engine room air intake louvers with foldable awnings that double as shipping covers
    • Two (2) lockable personnel doors with panic releases
    • Interior walls and ceilings insulated with 50 mm of acoustic paneling
    • Side bus bar access door with external access load cable connections
    • Shore power via distribution block connections for jacket water heater, battery charger, and generator Anti-condensation Heaters
    • Four (4) DC lights with 60-min timer
    • Single-wall, 378-L (100gal) fuel tank; certified to BS799-5
    • Solenoid fuel-fill control valve for automated tank filling
    • Triple, primary fuel filters with integral water separators and service valves for on-the-fly changes
    • Sound attenuated to 83 dBA (50 Hz) / 85 dBA (60 Hz) at 7m (23 ft)
    • Two (2) 1400-CCA, Group 4D, maintenance-free batteries and 50-Amp battery charger
    • Insulated exhaust silencer with 1.8m (6ft) stainless steel exhaust stack for increased site power density
    • Engine vibration isolators
    • Easy drain access to standard fluids
    • Standard Cat decals and painted Cat Power Module White
  • Cooling
    • Cooling package provides 40°C (104F) ambient capability at 50 Hz, or 42°C (108F) capability at 60 Hz at the IPP Rating at 750m (2,460 ft) above sea level
    • Vertical, non-stacked radiator cores with dimpled fins and vertical air discharge
    • Variable frequency fan drive with smart fan control
    • Cat Extended Life Coolant (ELC)
  • Generator Controls and Protection
    • EMCP 4.3 generator set mounted controller
    • Automatic start/stop with cool down timer
    • Generator Protection features: 25, 32, 40, 50/51, 27/59, 81 O/U
    • AGC-4 provides voltage and frequency adjust, base load / PF / load sharing / synchouronizer, auto start / stop control & generator CB control, SCADA Interface (Ethernet), fuel level Indications & alarms, and fuel tank fuel transfer control
    • Reverse compatibility for interface to legacy power modules
    • 100 kAIC, 4000A-Frame generator circuit breaker with LSIG trip unit
    • Multi-mode operation: Island (kW/kVAR sharing), Base load power, Power management with multiple units
    • Manual and automatic paralleling capability
    • Metering display: voltage, current, frequency, power factor, kW, WHM, kVAR, and synchouroscope
  • Quality
    • Factory testing of complete power module
    • CE Certified, NEMA, ISO and IEEE standards
    • O&M manuals